HL-5030
Công tắc hành trình Omron
Economical, Miniature Limit Switch Boasting Rigid Construction
last update: September 24, 2012
| Actuator | Model | |
|---|---|---|
| Roller lever | ![]() | HL-5000 * |
| Adjustable roller lever | ![]() | HL-5030 * |
| Adjustable rod lever | ![]() | HL-5050 * |
| Sealed plunger | ![]() | HL-5100 * |
| Sealed roller plunger | ![]() | HL-5200 |
| Coil spring | ![]() | HL-5300 |
standards. When placing an order, add the code to the model number to indicate if ground terminal/M5 tapping on the
rear side is required.
-G: with ground terminal/M5 tapping on the rear side.
Ratings
| Rated voltage | Non-inductive load (A) | Inductive load (A) | ||||||
|---|---|---|---|---|---|---|---|---|
| Resistive load | Lamp load | Inductive load | Motor load | |||||
| NC | NO | NC | NO | NC | NO | NC | NO | |
| 125 VAC 250 VAC | 5 5 | 1.5 1 | 0.7 0.5 | 3 3 | 2 1.5 | 1 0.8 | ||
| 12 VDC 24 VDC 125 VDC 250 VDC | 5 5 | 3 3 | 4 4 | 3 3 | ||||
| 0.4 0.4 | 0.2 0.2 | – | – | – | ||||
2. Inductive loads have a power factor of 0.4 min. (AC) and a time constant of 7 ms max. (DC).
3. Lamp load has an inrush current of 10 times the steady-state current.
4. Motor load has an inrush current of 6 times the steady-state current.
| Inrush current | NC | 24 A max. |
|---|---|---|
| NO | 12 A max. |
Characteristics
| Degree of protection | IP65 | |
|---|---|---|
| Durability * | Mechanical | 10,000,000 operations min. (under rated conditions) |
| Electrical | See the following Electrical Durability. | |
| Operating speed | 5 mm/s to 0.5 m/s | |
| Operating frequency | Mechanical | 120 operations/min |
| Electrical | 30 operations/min | |
| Insulation resistance | 100 MΩ min. (at 500 VDC) | |
| Contact resistance | 25 mΩ max. (initial value) | |
| Dielectric strength | 1,000 VAC, 50/60 Hz for 1 min between terminals of the same polarity | |
| 1,500 VAC, 50/60 Hz for 1 min between current-carrying metal parts and ground | ||
| 1,500 VAC, 50/60 Hz for 1 min between each terminal and non-current-carrying metal part | ||
| Rated frequency | 50/60 Hz | |
| Vibration resistance | Malfunction | 10 to 55 Hz, 1.5-mm double amplitude |
| Shock resistance | Destruction | 1,000 m/s2 max. |
| Malfunction | 300 m/s2 max. | |
| Ambient operating temperature | -5°C to +65°C (with no icing) | |
| Ambient operating humidity | 35% to 95%RH | |
| Weight | Approx. 130 to 190 g | |
2. The above characteristics may vary depending on the model. For further details, contact your OMRON sales
representative.
* The values are calculated at an operating temperature of +5°C to +35°C, and an operating humidity of 40% to 70%RH.
Contact your OMRON sales representative for more detailed information on other operating environments.